0 members (),
236
guests, and
39
robots. |
|
Key:
Admin,
Global Mod,
Mod
|
|
|
Forums39
Topics49,918
Posts838,254
Members9,638
| |
Most Online1,063 Jun 14th, 2026
|
|
|
|
Joined: Feb 2016
Posts: 8,706 Likes: 416
Needs to Get Out More!
|
Needs to Get Out More!
Joined: Feb 2016
Posts: 8,706 Likes: 416 |
I plugged in a friends EV who was staying overnight via an extension lead via three pin plug into my garage wall socket. Blew the main house fuse after 40 mins. Most inconvenient. And the extension lead cable insulation was melting. I know I should have unwound the extension cable completely.
I will stick with my +8 Helped a friend connect his 3kW EV charger up over Christmas. It specifically says not to use extension leads irrespective of cable gauge, so we found a 13 amp socket in his outbuilding on a dedicated ring main (which is also a requirement) which allowed the charge cable to reach his car. I doubt these chargers are constant power devices but if they were would draw more than the expected 12.5 amps due to volt drop along the length of any extension lead used.
Richard
2018 Roadster 3.7 1966 Land Rover S2a 88 2024 Royal Enfield Guerrilla 450 1945 Guzzi Airone
|
|
|
|
|
Joined: Nov 2015
Posts: 8,712 Likes: 502
Just barreling along Needs to Get Out More!
|
Just barreling along Needs to Get Out More!
Joined: Nov 2015
Posts: 8,712 Likes: 502 |
I plugged in a friends EV who was staying overnight via an extension lead via three pin plug into my garage wall socket. Blew the main house fuse after 40 mins. Most inconvenient. And the extension lead cable insulation was melting. I know I should have unwound the extension cable completely.
I will stick with my +8 It's good news the fuse (or RCD) tripped, saving you from a potentially dangerous fire or mains short in the coiled up extension cable
Jon M
|
|
|
|
|
Joined: Jul 2019
Posts: 5,473 Likes: 476
Charter Member
|
Charter Member
Joined: Jul 2019
Posts: 5,473 Likes: 476 |
I plugged in a friends EV who was staying overnight via an extension lead via three pin plug into my garage wall socket. Blew the main house fuse after 40 mins. Most inconvenient. And the extension lead cable insulation was melting. I know I should have unwound the extension cable completely.
I will stick with my +8 It's good news the fuse (or RCD) tripped, saving you from a potentially dangerous fire or mains short in the coiled up extension cable Might be worth checking the protection on your garage, as ideally a fault on anything connected via a13 amp plug should ideally disconnect before the last line of defence which is usually the main fuse supplying the house...?
|
|
|
|
|
Joined: Feb 2016
Posts: 8,706 Likes: 416
Needs to Get Out More!
|
Needs to Get Out More!
Joined: Feb 2016
Posts: 8,706 Likes: 416 |
I plugged in a friends EV who was staying overnight via an extension lead via three pin plug into my garage wall socket. Blew the main house fuse after 40 mins. Most inconvenient. And the extension lead cable insulation was melting. I know I should have unwound the extension cable completely.
I will stick with my +8 It's good news the fuse (or RCD) tripped, saving you from a potentially dangerous fire or mains short in the coiled up extension cable I think we are talking current overload protection here so an RCD by itself, which trips on current imbalance between live and neutral, wouldn't solve the problem. For a garage a residual current breaker with overload protection (RCBO) would be useful combining both forms of protection.
Richard
2018 Roadster 3.7 1966 Land Rover S2a 88 2024 Royal Enfield Guerrilla 450 1945 Guzzi Airone
|
|
|
|
|
Joined: Mar 2009
Posts: 11,536 Likes: 321
Smile, it confuses them Member of the Inner Circle
|
Smile, it confuses them Member of the Inner Circle
Joined: Mar 2009
Posts: 11,536 Likes: 321 |
I did the same when I was young, 13amp coiled mains extension lead running a high power space heater. I had some things I needed heating up prior to working on them. Left it running in the garage and all the lights went out. The coil was to hot to handle.
In those days the outer coating of the lead was often rubber or some rubber related item and it had heated up a lot. Whilst the problem was fixed the smell of molten rubber hung around for a long time. I was lucky not to have a fire! I can barely remember the days of youth and daft in equal parts.
Everyone loves a Morgan. Even me, unless it's broken again.
|
|
|
|
|
Joined: Dec 2009
Posts: 37,493 Likes: 994
Tricky Dicky Member of the Inner Circle
|
Tricky Dicky Member of the Inner Circle
Joined: Dec 2009
Posts: 37,493 Likes: 994 |
I plugged in a friends EV who was staying overnight via an extension lead via three pin plug into my garage wall socket. Blew the main house fuse after 40 mins. Most inconvenient. And the extension lead cable insulation was melting. I know I should have unwound the extension cable completely.
I will stick with my +8 It's good news the fuse (or RCD) tripped, saving you from a potentially dangerous fire or mains short in the coiled up extension cable I think we are talking current overload protection here so an RCD by itself, which trips on current imbalance between live and neutral, wouldn't solve the problem. For a garage a residual current breaker with overload protection (RCBO) would be useful combining both forms of protection. Spot on that's what I fitted on my garage spur, better safe than sorry damp concrete is not overly forgiving - it doesn't stop you going arse over tit and falling on your barn door toolbox edge though with your nose and upper lip needing 5 stitches at our (then) community hospital with no anaesthetic which concentrated the mind a little, still better than a root canal though.