Domestic supply is only rated at 9kw per hour
Sorry ewn, 9KW per hour makes no sense, wattage is a delivery of power (energy per second).
Max current rating on a UK domestic consumer unit is 100A, beyond that you need multiple supply points / consumer units at the same location (not a problem, we have 2) and for very high consumption you can go 3-phase.
100A means that at 240V you could in theory charge at 24KW, but you'd have to leave a bit to enable your other homes systems to run and you would need dedicated wiring to the charge point.